TECHNICAL DATA:

  • Supply voltage 220 / 240 V (-15... +10%)50 Hz (40 - 60 Hz)
  • Fuse rating 10 A rapid or 6 A slow
  • Power consumption 5 VA
  • Max. current peroutput terminal 4 A
  • Max. current total 6 A
  • Pre-ignition time 15 or 10 sec.
  • Delay, post-ignition time none
  • Safety interval nominal 5 or 10 sec.
  • Safety interval max. 10 or 20 sec.2nd stage delay approx. 20 sec.
  • Reset delay after lockout approx. 60 sec.
  • Permissible ambient temperature -20° C to +60° C
  • Sensitivity 1.5 µA
  • Min. ionisation current required 2 - 3 µA
  • Ionisation probe insulation probe - earthgreater than 50 MΩ
  • Stray capacitance probe - earthless than 1000 pF(max. 20 m cable)
  • Insulation standard IP 44
  • Weight incl. baseplate 250 g
  • Mounting attitude any

 