Honeywell TFI 812.2 mod.10
Honeywell TFI 812.2 mod.10
TECHNICAL DATA:
- Supply voltage 220 / 240 V (-15... +10%)50 Hz (40 - 60 Hz)
- Fuse rating 10 A rapid or 6 A slow
- Power consumption 5 VA
- Max. current peroutput terminal 4 A
- Max. current total 6 A
- Pre-ignition time 15 or 10 sec.
- Delay, post-ignition time none
- Safety interval nominal 5 or 10 sec.
- Safety interval max. 10 or 20 sec.2nd stage delay approx. 20 sec.
- Reset delay after lockout approx. 60 sec.
- Permissible ambient temperature -20° C to +60° C
- Sensitivity 1.5 µA
- Min. ionisation current required 2 - 3 µA
- Ionisation probe insulation probe - earthgreater than 50 MΩ
- Stray capacitance probe - earthless than 1000 pF(max. 20 m cable)
- Insulation standard IP 44
- Weight incl. baseplate 250 g
- Mounting attitude any