Solenoid Valves VAS

 Solenoid ValvesVAS

Overvivew Spec

  • The gas must be dry in all temperaturesand must not condense.
  • Max. inlet pressure pe: max. 500 mbar.
  • Flow adjustment limits the maximum flowvolume between 20 and 100%. The settingcan be monitored on an indicator.
  • Opening time:VAS../N quick opening: ≤ 0.5 s;VAS../L slow opening: approx. 10 s.
  • Closing time:Quick closing: < 1 s.
  • Ambient temperature: -20 – +60°C,no condensation permitted.
  • Class A safety valve pursuant to EN 161.
  • Mains voltage:
    230 V AC, +10/-15%, 50/60 Hz;
    120 V AC, +10/-15%, 50/60 Hz;
    24 V DC, +20/-15%.